Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/29/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
10/29/2024 | Commercial Plumbing | REQUIRES RESUBMIT | 1. A gas-fired tankless water heater shall not be installed in a bathroom unless it is a direct vent appliance installed per the manufacturer’s instructions and its listing. Provide the specifications for the proposed tankless water heater. Reference: Sections 301.3, 303.1, and 303.3, IFGC 2018. 2. If the proposed tankless water heater is not a like-for-like replacement, provide: (1) The location of the gas meter (2) The gas delivery pressure (e.g., 7” WG, 2 PSIG, or 5 PSIG) (3) The gas load for each piece of equipment served by the gas meter in BTUH (4) The developed pipe length from the meter to each piece of equipment (5) The size and material of each pipe segment. (6) The location and downstream pressure of any pressure reducing valves. |
||