Permit Number: TC-COM-1024-01982
Parcel: 117040730

Address:
605 N 4TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1024-01982
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2024 Commercial Electrical APPROVED
11/21/2024 Site Engineering APPROVED
12/02/2024 Site Zoning APPROVED
11/25/2024 Historic NOT REQUIRED The project is outside HPZ. Located in the 4th Avenue National Historic District. Also it is an interior remodel. NO HPZ review required
Contact Michael.Taku@tucsonaz.gov
12/02/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/14/2024 Commercial Mechanical REQUIRES RESUBMIT Sheet A1 For questions in regards to plan review comments, please contact Bill McClellan by email at bmcclellan@willdan.com or cell(928)580-3179. all applicable comments followed by the initials (BM)
11/14/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Sheet P2 Provide for review, typical detail and notes for sediment trap at each appliance if not incorporated as part of the appliance to include location of trap to be downstream of the valve. 2018 IFGC 408.4
11/14/2024 Commercial Structural REQUIRES RESUBMIT 1. Sheet A7 Provide complete wall section framing detail for new support walls to include floor anchoring and lateral bracing / connection to existing wall or structure. Incomplete. 2018 IBC 107.2.1 (BM)
2. Sheet A7 Typical Hood support detail per manufacture identifies a minimum of 4 support rods along each long side of hood and additional support rods for supply air plenum section. Clarify with manufacture for alternate support methods to comply with proposed design of three rods and clips to wall. 2018 IBC 107.2.1 (BM)
[ Ver. 2 ] [Edited By Bill McClellan]
3. Sheet A6 Provide on plans ceiling framing detail or notes for new hood as applicable for new hood dimensions and support system. Not clear on plans. 2018 IBC 107.2.1 (BM)
11/17/2024 Fire New Construction REVIEW COMPLETED
10/21/2024 PDSD Application Completeness Express REVIEW COMPLETED