Permit Number: TC-COM-1024-01972
Parcel: 11309224B

Address:
825 E GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-1024-01972
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2024 Commercial Mechanical APPROVED
11/06/2024 Site Zoning APPROVED
10/30/2024 Site Engineering NOT REQUIRED
11/06/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
10/30/2024 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Building Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.
1. Please amend the plan to indicate Furniture Store Expansion will require a permit and result in a new C of O.
2. Please amend plans to show required 10” Kick Plate 404.2.9 2009 ICC A117.1
A. Door surfaces within 10 inches of the floor, measured vertically, shall be a smooth surface on the push side extending the full width of the door. Cavities created by added kick plates shall be capped.
3. Please amend plans to show accessible service and sales counters on plans. IBC 107.2.1 and 2009 ICC A117.1 Chapter 9
4. Please amend plans to provide elevation detail of drinking fountain showing cane detectability or provide alcove to ensure drinking fountain is not a protruding object IBC1003.3
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
10/31/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Provide complete compliance with the 2018 IECC for the lighting.
11/04/2024 Commercial Plumbing REQUIRES RESUBMIT 1. If the “beverage dispenser” is to be used in lieu of a drinking fountain, show the installation of a permanently mounted disposable cup dispenser. The cup dispenser shall be located adjacent to the water dispenser with the dispensing end between 34” and 48” above the finished floor. See: https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/2008-21_e_drinkingfountainpolicy.pdf
2. Clarify how the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
10/31/2024 Fire New Construction REVIEW COMPLETED
10/17/2024 PDSD Application Completeness REVIEW COMPLETED