Permit Number: TC-COM-1024-01957
Parcel: 12405007B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-1024-01957
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2024 Commercial Mechanical APPROVED
10/29/2024 Commercial Plumbing APPROVED
10/29/2024 Site Engineering APPROVED
10/28/2024 Site Zoning APPROVED
10/30/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
10/30/2024 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Building Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.
1. Please provide an existing/demolition floor plan to verify the overall scope of demolition work that is proposed. IBC 107.2.1
2. Please amend plans to provide a reflected ceiling plan including ceiling finish elevations. IBC 107.2.1
3. Please amend wall details plans to note or otherwise indicate the method of fastening and bracing new walls at the floor. Additionally, provide a wall type detail for each new wall to include, but not be limited to, interior wall coverings and finishes. IBC 107.2.1
A. Further, related if applicable, please provide engineering or metal stud table to show how unbraced Interior walls and partitions that exceed 6 feet in height, including finish materials, shall have adequate strength and stiffness to resist the loads to which they are subjected but not less than a horizontal load of 5 psf. IBC 1607.15.
4. Please amend plans to indicate if this building contains more than one occupancy classification and if so, identify the mixed occupancy methodology as nonseparated, separated. IBC 508.1
5. Related to the above comment, please indicate the occupancy group of the adjacent tenant and if separated, indicate the fire-resistive rating of the fire barrier. IBC 508.4
6. Please amend plans to include an interior finish schedule to specify the classification for fire and smoke. Please include floors, walls and ceilings. IBC 803.1, IBC 804.1
7. Please amend plans to provide accessible details and enlarged drawings for the accessible changing room. Please provide clear floor space (305), coat hooks, fitting-room bench configuration allowing for transfer (803.4) and show bench dimensions (903). Even though the bench is to be supplied by the tenant the plans need to indicate a code compliant bench. Further, the C of O cannot be issued until the bench is in place. IBC 107.2.1, 2009 ICC A117.1 803 & 903
8 Please amend plans note or otherwise specify the technical accessible requirements for sales counters and service counters. 2009 ICC A117.1 Chapter 9 For example, height

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
10/28/2024 Commercial Electrical REQUIRES RESUBMIT Please revise the lighting Comcheck to the 2018 version.
10/30/2024 Fire New Construction REQUIRES RESUBMIT Resolve building comments.
questions: patricia.shelton@tucsonaz.gov
10/15/2024 PDSD Application Completeness REVIEW COMPLETED