Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1024-01945
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/29/2024 | Commercial Electrical | APPROVED | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Denied Reason: Date Completed : 10/24/2024 11:17:55 PM 1. GENERAL - UPDATES: For project updates, please submit sheets with all changes clearly marked in revision clouds. Please provide a written response to each comment; updates without a clear response to all comments may not be reviewed. If you have any questions regarding the comments, you may contact me directly. Updates may result in additional comments. 2. GENERAL - FIRM REGISTRATION: Per the Arizona Revised Statutes, Chapter 32, Rule 141, a firm shall not engage in the practice of any board-regulated profession or occupation unless the firm is registered with the board”. Please ensure that Hohbach-Lewin, Inc has been properly registered with the State of Arizona under this provision. Refer to the Arizona State Board of Technical Registration (https://btr.az.gov/public/registered-firm-branch-search) for more information. 3. S100 - WIND DESIGN CRITERIA: Section 1603.1.4 of the 2018 International Building Code lists the wind design criteria that must be provided on the construction documents. Please revise the structural general notes to include the following: i. Basic design wind speed, V, expressed in miles per hour ii. Wind Exposure iii. Design wind pressures to be used for exterior component and cladding materials, expressed in pounds per square foot 4. STRUCTURAL CALCULATIONS - ENGINEER'S SEAL: Engineers in Arizona are required to seal, sign, and date construction documents that they prepare for regulatory approval, permitting, or construction. The submitted structural calculations have not submitted without an engineer's seal. Please revise and resubmit. Building(B) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Approved Reason: Date Completed : 10/21/2024 4:43:37 AM Mechanical(M) Reviewer Jake Doub jdoub@safebuilt.com Approved Reason: Date Completed : 10/26/2024 8:09:28 PM Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved with Comments Reason: Date Completed : 10/26/2024 11:03:24 AM 1. E-101 Key Note #2 should be revised to more accurately call out the other 18 contact LCP panel. 2. as two Key Note #5s. Should renumber/remove extra. 3. E-101 should provide missing Key Note 11 description. 4. E-201 Security Key Note S2 is used at numerous locations. Should provide missing Key Note description. Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Approved Reason: Date Completed : 10/28/2024 10:04:59 PM |
||
10/29/2024 | Commercial Mechanical | APPROVED | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Denied Reason: Date Completed : 10/24/2024 11:17:55 PM 1. GENERAL - UPDATES: For project updates, please submit sheets with all changes clearly marked in revision clouds. Please provide a written response to each comment; updates without a clear response to all comments may not be reviewed. If you have any questions regarding the comments, you may contact me directly. Updates may result in additional comments. 2. GENERAL - FIRM REGISTRATION: Per the Arizona Revised Statutes, Chapter 32, Rule 141, a firm shall not engage in the practice of any board-regulated profession or occupation unless the firm is registered with the board”. Please ensure that Hohbach-Lewin, Inc has been properly registered with the State of Arizona under this provision. Refer to the Arizona State Board of Technical Registration (https://btr.az.gov/public/registered-firm-branch-search) for more information. 3. S100 - WIND DESIGN CRITERIA: Section 1603.1.4 of the 2018 International Building Code lists the wind design criteria that must be provided on the construction documents. Please revise the structural general notes to include the following: i. Basic design wind speed, V, expressed in miles per hour ii. Wind Exposure iii. Design wind pressures to be used for exterior component and cladding materials, expressed in pounds per square foot 4. STRUCTURAL CALCULATIONS - ENGINEER'S SEAL: Engineers in Arizona are required to seal, sign, and date construction documents that they prepare for regulatory approval, permitting, or construction. The submitted structural calculations have not submitted without an engineer's seal. Please revise and resubmit. Building(B) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Approved Reason: Date Completed : 10/21/2024 4:43:37 AM Mechanical(M) Reviewer Jake Doub jdoub@safebuilt.com Approved Reason: Date Completed : 10/26/2024 8:09:28 PM Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved with Comments Reason: Date Completed : 10/26/2024 11:03:24 AM 1. E-101 Key Note #2 should be revised to more accurately call out the other 18 contact LCP panel. 2. as two Key Note #5s. Should renumber/remove extra. 3. E-101 should provide missing Key Note 11 description. 4. E-201 Security Key Note S2 is used at numerous locations. Should provide missing Key Note description. Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Approved Reason: Date Completed : 10/28/2024 10:04:59 PM |
||
10/29/2024 | Commercial Plumbing | APPROVED | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Denied Reason: Date Completed : 10/24/2024 11:17:55 PM 1. GENERAL - UPDATES: For project updates, please submit sheets with all changes clearly marked in revision clouds. Please provide a written response to each comment; updates without a clear response to all comments may not be reviewed. If you have any questions regarding the comments, you may contact me directly. Updates may result in additional comments. 2. GENERAL - FIRM REGISTRATION: Per the Arizona Revised Statutes, Chapter 32, Rule 141, a firm shall not engage in the practice of any board-regulated profession or occupation unless the firm is registered with the board”. Please ensure that Hohbach-Lewin, Inc has been properly registered with the State of Arizona under this provision. Refer to the Arizona State Board of Technical Registration (https://btr.az.gov/public/registered-firm-branch-search) for more information. 3. S100 - WIND DESIGN CRITERIA: Section 1603.1.4 of the 2018 International Building Code lists the wind design criteria that must be provided on the construction documents. Please revise the structural general notes to include the following: i. Basic design wind speed, V, expressed in miles per hour ii. Wind Exposure iii. Design wind pressures to be used for exterior component and cladding materials, expressed in pounds per square foot 4. STRUCTURAL CALCULATIONS - ENGINEER'S SEAL: Engineers in Arizona are required to seal, sign, and date construction documents that they prepare for regulatory approval, permitting, or construction. The submitted structural calculations have not submitted without an engineer's seal. Please revise and resubmit. Building(B) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Approved Reason: Date Completed : 10/21/2024 4:43:37 AM Mechanical(M) Reviewer Jake Doub jdoub@safebuilt.com Approved Reason: Date Completed : 10/26/2024 8:09:28 PM Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved with Comments Reason: Date Completed : 10/26/2024 11:03:24 AM 1. E-101 Key Note #2 should be revised to more accurately call out the other 18 contact LCP panel. 2. as two Key Note #5s. Should renumber/remove extra. 3. E-101 should provide missing Key Note 11 description. 4. E-201 Security Key Note S2 is used at numerous locations. Should provide missing Key Note description. Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Approved Reason: Date Completed : 10/28/2024 10:04:59 PM |
||
11/18/2024 | Site Zoning | APPROVED | |||
11/18/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
10/29/2024 | Commercial Structural | REQUIRES RESUBMIT | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Denied Reason: Date Completed : 10/24/2024 11:17:55 PM 1. GENERAL - UPDATES: For project updates, please submit sheets with all changes clearly marked in revision clouds. Please provide a written response to each comment; updates without a clear response to all comments may not be reviewed. If you have any questions regarding the comments, you may contact me directly. Updates may result in additional comments. 2. GENERAL - FIRM REGISTRATION: Per the Arizona Revised Statutes, Chapter 32, Rule 141, a firm shall not engage in the practice of any board-regulated profession or occupation unless the firm is registered with the board”. Please ensure that Hohbach-Lewin, Inc has been properly registered with the State of Arizona under this provision. Refer to the Arizona State Board of Technical Registration (https://btr.az.gov/public/registered-firm-branch-search) for more information. 3. S100 - WIND DESIGN CRITERIA: Section 1603.1.4 of the 2018 International Building Code lists the wind design criteria that must be provided on the construction documents. Please revise the structural general notes to include the following: i. Basic design wind speed, V, expressed in miles per hour ii. Wind Exposure iii. Design wind pressures to be used for exterior component and cladding materials, expressed in pounds per square foot 4. STRUCTURAL CALCULATIONS - ENGINEER'S SEAL: Engineers in Arizona are required to seal, sign, and date construction documents that they prepare for regulatory approval, permitting, or construction. The submitted structural calculations have not submitted without an engineer's seal. Please revise and resubmit. Building(B) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Approved Reason: Date Completed : 10/21/2024 4:43:37 AM Mechanical(M) Reviewer Jake Doub jdoub@safebuilt.com Approved Reason: Date Completed : 10/26/2024 8:09:28 PM Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved with Comments Reason: Date Completed : 10/26/2024 11:03:24 AM 1. E-101 Key Note #2 should be revised to more accurately call out the other 18 contact LCP panel. 2. as two Key Note #5s. Should renumber/remove extra. 3. E-101 should provide missing Key Note 11 description. 4. E-201 Security Key Note S2 is used at numerous locations. Should provide missing Key Note description. Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Approved Reason: Date Completed : 10/28/2024 10:04:59 PM |
||
11/13/2024 | Fire New Construction | REVIEW COMPLETED | |||
10/14/2024 | PDSD Application Completeness | REVIEW COMPLETED | |||
11/15/2024 | Site Engineering | REVIEW COMPLETED |