Permit Number: TC-COM-1024-01944
Parcel: 13316013E

Address:
6610 E GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1024-01944
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2024 Site Zoning APPROVED
10/29/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
10/29/2024 Site Engineering PENDING ASSIGNMENT
10/24/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Provide complete compliance 2012 City of Tucson Outdoor Lighting Code (OLC) for the exterior luminaires. See section 104 for plan submittal requirements.

2 All Signage, Menu boards to be reviewed for Sign Code and Outdoor Lighting Code under Sign permit. Please note this on the site lighting plan.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC, 2012 City of Tucson Outdoor Lighting Code (OLC), City of Tucson Commercial Plan Submittal Requirements.
10/24/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Coordinate the kitchen equipment layout with the hood types. The kitchen equipment layout shows the heavy-duty appliances located under the hood designed for medium-duty appliances. Reference: Section 507.5, IMC 2018.
2. Evaporative cooling systems that do not include water recycling or reuse systems are prohibited by the Arizona Revised Statues, ARS 45-313. Verify that the evaporative cooling section of the specified make-up air unit, MAU-1, includes recirculation of the water.
3. Show that the walk-in cooler and the walk-in freezer meet the construction requirements of Section C403.10.2, IECC 2018.
4. Show that the walk-in cooler and the walk-in freezer meet the efficiency requirements of Section C403.10.2.1, IECC 2018.
10/28/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Clarify the intent of Detail 7/P3.0. It calls for the automatic gas shut-off valve to be located 12” above the ceiling but a note on the same detail states that no valves shall be installed above the ceiling. Reference: Section 107.2.1, IBC 2018.
2. Clarify the intent of Detail 10/P3.0. It calls for PVC pipe to be used for the condensate drain in the walk-in cooler but also states that no PVC pipe is to be used. Reference: Section 107.2.1, IBC 2018.
10/28/2024 Commercial Structural REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0924-01866
ADDRESS/PARCEL: (2661 N 1ST AV TUCSON, AZ 85719)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter.
COMMENTS:
1. Sheet T1.0 - Restaurant is A-2 occupancy classification, please confirm & correct your code analysis.
2. Sheet T1.0 - You indicate sprinkler and alarm is provided. Please confirm (your means of egress table indicates 200' travel distance which is without sprinkler). Should there be no sprinkler, 6,000 sf max allowable area (you currently show 24,000 sf).
3. Sheet SP1.0 - Handicap sign post is not identified on site plan. Please locate and label on the drawing.
4. Sheet A0.1 - Your Equipment Plan shows 40 seats. Please verify and confirm, make corrections as necessary.
a. Panic and fire exit hardware on swinging doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock other than panic hardware or fire exit hardware. IBC 1010.1.10 Please include these in your drawings should there be 50 or more occupants.
5. Sheet A1.0 - Sign: This Door To Remain Unlocked When This Space Is Occupied. IBC 1010.1.9.4 to be installed at the front door and back door. Please add this information in your drawing.
6. Sheet A1.3 - Identify whether NSF equipment or not.
7. The force for pushing or pulling open interior swinging egress doors, other than fire doors, shall not exceed 5 pounds. Per IBC section 1010.1.3 Please indicate this in your drawing.
8. Please resubmit.
10/14/2024 Fire New Construction REQUIRES RESUBMIT -Provide the occupancy classification in the code analysis. It currently has C2 which is not an occupancy classification.
john.vincent@tucsonaz.gov
5203495581
10/11/2024 PDSD Application Completeness REVIEW COMPLETED