Permit Number: TC-COM-1024-01935
Parcel: 119180820

Address:
802 W AJO WY

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1024-01935
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2024 Commercial Structural APPROVED
11/19/2024 Site Zoning APPROVED
11/07/2024 Commercial Mechanical NOT REQUIRED
11/12/2024 Site Engineering NOT REQUIRED
11/19/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
11/08/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical review comments and provide a written response.

1 Please provide complete electrical power and lighting plans, sealed by a registrant registered in the state of Arizona. The registrant stamp on the submitted electrical plans is not legible where applied. See City of Tucson Electrical Commercial Plan Submittal Requirements can be downloaded at www.tucsonaz.gov/pdsd; Include branch circuit and panel designations for all electrical devices and luminaires that correlate with complete panel schedules, NEC 408.4.

2 Provide complete compliance with the 2018 IECC for lighting and controls.

Ref; 2018 IBC sec. 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code
11/05/2024 Fire New Construction REVIEW COMPLETED
10/10/2024 PDSD Application Completeness REVIEW COMPLETED