Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1024-01935
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/05/2024 | Commercial Structural | APPROVED | |||
11/19/2024 | Site Zoning | APPROVED | |||
11/07/2024 | Commercial Mechanical | NOT REQUIRED | |||
11/12/2024 | Site Engineering | NOT REQUIRED | |||
11/19/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/08/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical review comments and provide a written response. 1 Please provide complete electrical power and lighting plans, sealed by a registrant registered in the state of Arizona. The registrant stamp on the submitted electrical plans is not legible where applied. See City of Tucson Electrical Commercial Plan Submittal Requirements can be downloaded at www.tucsonaz.gov/pdsd; Include branch circuit and panel designations for all electrical devices and luminaires that correlate with complete panel schedules, NEC 408.4. 2 Provide complete compliance with the 2018 IECC for lighting and controls. Ref; 2018 IBC sec. 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code |
||
11/05/2024 | Fire New Construction | REVIEW COMPLETED | |||
10/10/2024 | PDSD Application Completeness | REVIEW COMPLETED |