Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1024-01933
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/05/2024 | Commercial Structural | APPROVED | |||
| 11/12/2024 | Site Engineering | APPROVED | |||
| 11/07/2024 | Commercial Mechanical | NOT REQUIRED | |||
| 11/07/2024 | Commercial Plumbing | NOT REQUIRED | |||
| 11/19/2024 | Site Zoning | NOT REQUIRED | |||
| 11/19/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/08/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Provide manufacturers cut sheets and highlight all applicable information for the EV Charging Stations. 2 Provide compliance with NEC art 240.87 (Arc Energy Reduction) verify equipped for the 1200 amp main breaker in the switchgear. REF; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
||
| 10/31/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 10/10/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |