Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-1024-01933
Parcel: 129043530

Address:
2150 E 15TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1024-01933
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2024 Commercial Structural APPROVED
11/12/2024 Site Engineering APPROVED
11/07/2024 Commercial Mechanical NOT REQUIRED
11/07/2024 Commercial Plumbing NOT REQUIRED
11/19/2024 Site Zoning NOT REQUIRED
11/19/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/08/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Provide manufacturers cut sheets and highlight all applicable information for the EV Charging Stations.

2 Provide compliance with NEC art 240.87 (Arc Energy Reduction) verify equipped for the 1200 amp main breaker in the switchgear.

REF; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
10/31/2024 Fire New Construction REVIEW COMPLETED
10/10/2024 PDSD Application Completeness Express REVIEW COMPLETED