11/19/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 The scope of work description to install (100 amp equipment) in the permit application does not correlate with the submitted electrical plan (200 amp) equipment. Please clarify or revise the scope of work and resubmit. REF; 2018 IBC section 107.2.1, 2017 NEC. |
||