Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-1024-01907
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/14/2025 | Commercial Plumbing | APPROVED | |||
| 04/14/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/14/2025 | Commercial Mechanical | REQUIRES RESUBMIT | Rooms 108 and 110 of suite 170 are receiving ventilation transferred entirely from rooms 109, 111, and 113. How is this transfer accomplished since all of the over-ventilated rooms have doors that will restrict the flow of air? Reference: Section 403.2.2, IMC 2018. | ||
| 03/24/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |