Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-1024-01907
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/14/2025 | Commercial Electrical | APPROVED | |||
| 03/01/2025 | Commercial Structural | APPROVED | |||
| 03/01/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/27/2025 | Commercial Mechanical | REQUIRES RESUBMIT | Comment not addressed. [Initial comment: Revise the mechanical design as required to avoid using the corridor in suite 190 as a return air duct. Reference: Section 601.2, IMC 2018.] | ||
| 02/27/2025 | Commercial Plumbing | REQUIRES RESUBMIT | Comment not addressed. [Initial comment: Provide waste and vent isometrics for the new work. Reference: Section 107.2.1, IBC 2018.] | ||
| 02/13/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |