Permit Number: TC-COM-1023-02560
Parcel: 135084450

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1023-02560
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/22/2023 Commercial Mechanical APPROVED
11/08/2023 Site Zoning APPROVED
11/22/2023 Commercial Plumbing NOT REQUIRED
11/22/2023 Site Engineering NOT REQUIRED
11/22/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
11/20/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

Please provide a detailed description in the electrical plans of the electrical scope of work proposed.

1. Verify that the unit sub panel is not located in the closet or bathroom, NEC 240.24(E)(D), 408.17. Could not verify by the photograph submitted. If it is in either location, please relocate to a code compliant location.

2. It appears that the unit was gutted out according to the photograph submitted. Verify required compliance with NEC art 210.8(A) for GFI protection of receptacle(s), NEC 210.12(A) for Arc Fault protection of branch circuits and all electrical outlets, NEC 406.4(D) for receptacle replacements along with NEC 406.12 for Tamper Resistant receptacle replacement. Provide electrical notes concerning these items on the plan for clarity.

3. If all the luminaires are being replaced provide a luminaire schedule locations and compliance with the 2018 IECC.

4. Provide compliance with the 2012 City of Tucson Outdoor Lighting Code if applicable.

2018 IBC section107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code.
11/21/2023 Commercial Structural REQUIRES RESUBMIT Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed.
1. Clearly identify & label the project location within the Site Plan.
2. 100 AMP subpanel is not allowed within closet.
The location and required working space of electrical panel boards and over current protection devices shall not be designated for storage. Such devices shall not be located in clothes closets, bathrooms, or over the steps of a stairway. E3405.4
Please relocate to a code compliant location.
3. Please resubmit.
11/13/2023 Fire New Construction REVIEW COMPLETED
11/06/2023 PDSD Application Completeness REVIEW COMPLETED