Permit Number: TC-COM-1023-02548
Parcel: 11704058C

Address:
401 E 5TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1023-02548
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/27/2023 Water - PDSD APPROVED MASTER SET LOCATED AT: TC-COM-1023-02548 (401 E 5TH ST)WITH REVIEWS TO BE PERFORMED ON: TC-COM-1023-02552 (602/604 N 4TH ST), TC-COM-1023-02553 (606 N 4TH ST) NOTE: PLANS & STRUCTURAL ARE THE SAME, HOWEVER, MECHANICALS ARE DIFFERENT ON EACH SUBMISSION.
Studio Session 892-766-982
12/01/2023 Historic NOT REQUIRED This property is listed as a contributor to the 4th Avenue Commercial National Register Historic District. Unless the project is participating in the Infill Incentive District (IID), Historic review is not required.
12/01/2023 Site Engineering NOT REQUIRED MASTER SET LOCATED AT: TC-COM-1023-02548 (401 E 5TH ST)WITH REVIEWS TO BE PERFORMED ON: TC-COM-1023-02552 (602/604 N 4TH ST), TC-COM-1023-02553 (606 N 4TH ST) NOTE: PLANS & STRUCTURAL ARE THE SAME, HOWEVER, MECHANICALS ARE DIFFERENT ON EACH SUBMISSION.
Studio Session 892-766-982
12/01/2023 Bldg Permits - Post Review PENDING ASSIGNMENT MASTER SET LOCATED AT: TC-COM-1023-02548 (401 E 5TH ST)WITH REVIEWS TO BE PERFORMED ON: TC-COM-1023-02552 (602/604 N 4TH ST), TC-COM-1023-02553 (606 N 4TH ST) NOTE: PLANS & STRUCTURAL ARE THE SAME, HOWEVER, MECHANICALS ARE DIFFERENT ON EACH SUBMISSION.
Studio Session 892-766-982
11/08/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/7/2023 5:32:47 PM
See the building review comments.



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/7/2023 5:31:14 PM
1) Sheet cs0.01 (Cover Sheet): No fire protection is noted but sheet P0.0 specifies that sprinklers are installed and modified. Please coordinate and clarify the details. Include details on the plans or deferred submittal. (2018 IBC section 107)

2) Sheet cs0.01 (Cover Sheet): The plumbing calculations have several incorrect entries. Unit 401: Bars require 1 water closet for each 40 occupants and any fraction of occupant - 2 water closets are required for each sex. Drinking fountains are
shown being provided but no drinking fountains are shown on the plans. Please correct the calculations. Unit 602/604: The calculations show that separate facilities are provided but only one unisex toilet room is shown on the plans. Drinking fountains are shown being provided but no drinking fountains are shown on the plans. Please correct the calculations. Unit 606: The male and female occupants are to be equally divided from the occupant load of the space and include any fraction of occupants - based on 27 occupants there would be 14 males and 14 females to be used in the calculations. Separate facilities are shown being provided but not included in the plans and would be required for 27 occupants - please revise the plans. Drinking fountains are shown being provided but no drinking fountains are shown on the plans. Please correct the calculations. (2018 IPC Table 403.1, section 403.2) Revise all affected sheets.

3) Sheet cs0.01 (Cover Sheet): The project scope of work falls under the level 3 alterations and spaces appear to have changed occupancy. Accessibility requirements apply to all areas. (2018 IEBC sections 305, 606, 901.1, 1001.1)

4) Sheet cs0.01 (Cover Sheet): Include the actual and allowed building height. (2018 IBC Chapter 5)

5) Sheet P1.0 (Plumbing Plans): Include the new and existing plumbing fixtures in the calculations and isometric. Show the grease interceptor and the fixtures connected to it. (2018 IPC section 106.3.1, amended section 1003.3)

6) Sheet P1.0 (Plumbing Plans): Separate toilet facilities and drinking fountain is not shown in unit 606. (2018 IPC Table 403.1, section 403.2)



Mechanical(M) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/7/2023 5:32:12 PM
See the building review comments.


Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/7/2023 5:31:55 PM
See the building review comments.



Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/7/2023 5:32:30 PM
See the building review comments.
12/01/2023 Fire New Construction REQUIRES RESUBMIT -Sheet CS0.01, fire protection, states no fire suppression provided however sheet g1.01 states full nfpa 13 fire sprinkler system is provided along with a fire alarm. Clarify if building has or will have a sprinkler system and/or fire alarm.
john.vincent@tucsonaz.gov
5203495581






MASTER SET LOCATED AT: TC-COM-1023-02548 (401 E 5TH ST)WITH REVIEWS TO BE PERFORMED ON: TC-COM-1023-02552 (602/604 N 4TH ST), TC-COM-1023-02553 (606 N 4TH ST) NOTE: PLANS & STRUCTURAL ARE THE SAME, HOWEVER, MECHANICALS ARE DIFFERENT ON EACH SUBMISSION.
Studio Session 892-766-982
11/22/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: TC-COM-1023-02548
401 E 5TH ST Zoning C-3

TRANSMITTAL DATE:‎November 22, 2023


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT: As you are proposing a new exterior door opening and this structure is a contributing structure. Historic Review is required. Please contact Jodie Brown (jodie.brown@tucsonaz.gov) or Michael Taku (michael.taku@tucsonaz.gov) for any questions. Zoning can not approve until the historic review has been approved.

If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
11/03/2023 PDSD Application Completeness REVIEW COMPLETED