Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1023-02529
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/22/2023 | Site Engineering | APPROVED | |||
11/02/2023 | Site Zoning | APPROVED | |||
11/22/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/07/2023 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Structural(S) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 11/6/2023 4:51:39 PM See the building review comments. Building(B) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 11/6/2023 4:50:24 PM 1) General: Provide the envelope construction details or COMcheck demonstrating compliance with the 2018 IECC section C402. 2) Sheet A.0.001 (Cover Sheet): Include the allowed vs actual building area, height, and number of stories. (2018 IBC sections 503, 504) 3) Sheet A.0.001 (Cover Sheet): Specify if fire alarms are being installed and the list of deferred submittals and special inspections. (2018 IBC section 107) 4) Sheet A.0.100 (Framing Plans): Show the uses of the adjacent spaces to determine if fire separation is required per 2018 IBC Table 508.4. Detail all fire rated walls and ceilings. 5) Sheets A.0.100 (Framing Plans), P.0.100 (Plumbing Plans): Show the accessible toilet room fixture clear floor spaces and turning spaces. (2009 ICC A117.1 sections 603.2.1, 606.2) 6) Sheet A.0.100 (Framing Plans): The required high-low drinking fountains are not shown on the plans. (2018 IPC section 410.3, 2018 IBC section 1109.5, 2018 IEBC section 1009.1, 2009 ICC A117.1 section 602) 7) Sheet A.1.721 (Dressing Room Details): Include the bench height on details B and C showing the requirements of 2009 ICC A117.1 section 903.5 are met. 8) Sheet A.1.721 (Dressing Room Details): The accessible dressing room does not have the required tuning space in the room when the curtain is closed. (2009 ICC A117.1 sections 304.3.2, 803.2) 9) Sheets M0.100 (Mechanical Plans), A.0.100: Show the rated walls and fire dampers where rated assemblies are penetrated by ducts. (2018 IBC section 717) 10) Sheet P.0.100 (Plumbing Drawings): Show the high-low accessible drinking fountain location. (2018 IPC section 410.3, 2018 IBC section 1109.5, 2018 IEBC section 1009.1, 2009 ICC A117.1 section 602) Mechanical(M) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 11/6/2023 4:51:08 PM See the building review comments Electrical(E) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 11/6/2023 4:50:54 PM See the building review comments. Plumbing(P) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 11/6/2023 4:51:22 PM See the building review comments. |
||
11/13/2023 | Fire New Construction | REVIEW COMPLETED | |||
10/31/2023 | PDSD Application Completeness | REVIEW COMPLETED |