Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-1023-02513
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/20/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/20/2024 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | 1. Provide an air balance report for the ventilation systems for the new restaurant (i.e. not just the test results of the duct smoke detectors). The report shall verify that the ventilation systems provide the airflow rates specified by the responsible engineer and by Sections 403.3 and 403,3,1,2, IMC 2018. Reference: Section 403.3.1.5, IMC 2018, as amended by the City of Tucson. 2. Provide the results of the capture and containment testing of the Type I hoods. Reference: Section 507.6.1, IMC 2018. |
||
| 05/16/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |