Review Details: RESTAMP - COMMERCIAL v.1
Permit Number - TC-COM-1023-02510
Review Name: RESTAMP - COMMERCIAL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/16/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/16/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 The electrical design has changed since the original electrical plan review approval in 2023. Indicate the following information on the electrical plan(s); a Conduit and conductor quantities, sizes and types between the utility meter and the New 122 Panel. b Available fault current at the service and the AIC ratings of all associated electrical service equipment. c Show the Grounding Electrode System and connection in the electrical one line diagram. Ref; 2018 IBC section 107.2.1, 2017 NEC |