Permit Number: TC-COM-1023-02510
Parcel: 111081410

Address:
3505 E GRANT RD

Review Status: Requires Resubmit

Review Details: RESTAMP - COMMERCIAL v.1

Permit Number - TC-COM-1023-02510
Review Name: RESTAMP - COMMERCIAL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/16/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 The electrical design has changed since the original electrical plan review approval in 2023. Indicate the following information on the electrical plan(s);

a Conduit and conductor quantities, sizes and types between the utility meter and the New 122 Panel.

b Available fault current at the service and the AIC ratings of all associated electrical service equipment.

c Show the Grounding Electrode System and connection in the electrical one line diagram.

Ref; 2018 IBC section 107.2.1, 2017 NEC