Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.4
Permit Number - TC-COM-1023-02509
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/28/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/28/2023 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Building(B) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 12/28/2023 4:44:58 PM Pending the approval of the other trades. Mechanical(M) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 12/28/2023 4:45:13 PM Pending the approval of the other trades Electrical(E) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 12/28/2023 4:44:15 PM 1) Unresolved - Sheet E.2 (Electrical Drawings): Show the GFCI protected receptacles for the kitchen, rooftop, exterior, and within 6ft of the sinks. (2017 NEC section 210.8(B)(2), (3), (4), and (5)) All kitchen single phase 150v and 50A or less and 3- phase 150V and 100A or less receptacles are required to be GFCI protected whether they serve countertop areas or not. All rooftop receptacles are to be GFCI protected. Please revise electrical details on sheet E.2. Plumbing(P) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 12/28/2023 4:45:29 PM Pending the approval of the other trades. |
||
| 12/27/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |