Permit Number: TC-COM-1023-02509
Parcel: 12308064A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1023-02509
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/08/2023 Site Zoning APPROVED
11/22/2023 Water - PDSD APPROVED
11/22/2023 Site Engineering NOT REQUIRED
11/22/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/02/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/2/2023 1:17:07 PM
See the building review comments.



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/2/2023 1:15:25 PM
1) Sheet G.1 (Cover Sheet): Include a brief scope of work. (2018 IBC section 107)
2) Sheet A.1 (Floor Plans): Include the accessible toilet room component, fixture and clear floor and turning space details and dimensions. (2009 ICC A117.1 sections 304, 305, 603, 603.2.2, 604, 606)

3) Sheet P1.0 (Plumbing Drawings): All sinks, floor sinks, mops sink, hand wash sinks, floor drains, etc. listed in the amended 2018 IPC section 1003.3 are to be connected to the grease interceptor. Hand sinks not connected to the grease
interceptor can include a sign specifying “HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED.” Please make revisions to all sheets and details.

4) Sheet E.2 (Electrical Drawings): Include the new or existing electrical service equipment details, main disconnect, one-line diagram, and show the required workspace dimensions for the equipment. (2017 NEC sections 110.26, 225.31, 225.32, 225.33)

5) Sheet E.2 (Electrical Drawings): Show the GFCI protected receptacles for the kitchen, rooftop, exterior, and within 6ft of the sinks. (2017 NEC section 210.8(B)(2), (3), (4), and (5))



Mechanical(M) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/2/2023 1:16:24 PM
See the building review comments.



Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/2/2023 1:15:55 PM
See the building review comments.



Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/2/2023 1:16:45 PM
See the building review comments
11/20/2023 Fire New Construction REVIEW COMPLETED
10/30/2023 PDSD Application Completeness Express REVIEW COMPLETED