Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1023-02505
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/15/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
07/23/2024 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Denied Reason: Date Completed : 7/17/2024 5:31:58 PM 1. Sheet LS101/First Floor Life Safety Plan: The outpatient therapy gym and the reception area are open to the corridor. While this is permitted, the open space is required to be provided with an automatic fire detection system. Also, the corridors are required to be protected by an automatic fire detection system or quick response sprinklers in the smoke compartment. No indication has been provided to the level of protection provided. Provide evidence of compliance in accordance with 2018 IBC Section 407.2.1 #2 and #3. 2. Sheet LS101/ Second Floor Life Safety Plan: The corridor that serves the following rooms doesn't appear to be protected properly; Conference Room (252), HR (251), Nurse Director (249), Rehab Director (247), CNO ( 245). Provide a properly protected corridor wall in accordance with 2018 IBC Section 407.3. 3. Sheet LS101/Life Safety Plans: Refuge areas are required for I-2 smoke compartments. However, no indication has been provided as of the location of these required refuge areas. Provide the location and the area calculations for the refuge areas in accordance with 2018 IBC Section 407.5.3. 4. Sheet LS102/Life Safety Plans: Refuge areas are required for I-2 smoke compartments. However, no indication has been provided as of the location of these required refuge areas. Provide the location and the area calculations for the refuge areas in accordance with 2018 IBC Section 407.5.3. 5. Sheet LS103/Occupant load calculations: Many of the occupant load factors are incorrect. Update the occupant load calculations using the correct occupant load factors in accordance with 2018 IBC Table 1004.5. Mechanical(M) Reviewer Jorge Valido jvalido@safebuilt.com Denied Reason: Date Completed : 7/23/2024 5:26:05 PM 1. General - Provide Energy Heat load Calculations - 2018 IECC Section C403.1.1 Calculation of heating and cooling loads. 2. General - Provide COMcheck Mechanical Compliance Certificate for all new equipment. - 2018 IECC Section C403.3.2 HVAC equipment performance requirements. 3. General - Provide details for: (1) Exhaust fan install detail, (2) Rectangular duct hanging detail, (3) Round duct hanging detail, (4) Refrigerant pipe hanging detail, (5) Piping fire rated penetration detail, (6) Fire damper detail. - 2018 IECC Section C103.2Information on construction documents. - 2018 IBC – Section [A]107.2.1Information on construction documents. 4. General - Provide details for: (1) Fire/Smoke damper detail (if applicable), (2) Condenser tie down detail, (3) RTU tie down detail, (4) Turning vane and or three piece 90 degree turn detail, (5) Linear diffuser install detail. - 2018 IECC Section C103.2Information on construction documents. - 2018 IBC – Section [A]107.2.1Information on construction documents. 5. General - Provide Manufacturer Listed Grease Hood plans - 2018 IMC Sections 506 COMMERCIAL KITCHEN HOOD VENTILATION SYSTEM DUCTS AND EXHAUST EQUIPMENT, 507 COMMERCIAL KITCHEN HOODS, 508 COMMERCIAL KITCHEN MAKEUP AIR. 6. General - Provide Listed Fire Suppression Plans - 2018 IMC Section 509 FIRE SUPPRESSION SYSTEMS. 7. Plan Sheet M150 - Show all Grease Hood and Make up air systems on roof plan. Provide clear dimensions showing distances from exhaust and makeup air openings, O/A openings. (if applicable) Provide clear dimensions from serviceable equipment and the edge of building. - 2018 IBC – Section [A]107.2.1Information on construction documents. - 2018 IMC Section 501.3.1 Location of exhaust outlets. - 2018 IMC Section [BE] 304.11 Guards. 8. Plan Sheet M110 - States on upper left "REFER TO SHEET M311 FOR ENLARGED MECHANICAL ROOM" There is no plan sheet M311 submitted - 2018 IBC – Section [A]107.2.1Information on construction documents. 9. Plan Sheet M210 - States on upper left "REFER TO SHEET M312 FOR ENLARGED MECHANICAL ROOM" There is no plan sheet M312 submitted - 2018 IBC – Section [A]107.2.1Information on construction documents. Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 7/22/2024 9:39:42 PM First Revised Plan Plumbing Review: 1). General: Need to address Bldg. plan review occupancy load comment #5. -2018 IPC 403.1 2). Plan Page A406: Missing fixture spacing measurements for lavatories & toilets. Add the sidewall to fixture center distances and the fixture to fixture center separation distances in accordance with -2018 IPC 404.2, 405.3.1 3). Missing affected plan page P002: The changes on revised plan page P100 will affect piping location & sizes on original plumbing site plan page P002. Send all affected plan pages with corrected revisions. -2018 IPC 106.3.1 4). Missing affected plan page P001: The revised plumbing pages appear to affect the sanitary & water piping calculation tables on plan page P001. Send all affected plan pages with corrected revisions. -2018 IPC 106.3.1 |
||
08/15/2024 | Fire New Construction | REQUIRES RESUBMIT | Address SafeBuilt comments. Questions: patricia.shelton@tucsonaz.gov |
||
08/15/2024 | Site Engineering | REQUIRES RESUBMIT | The associated development package TD-DEV-0623-00283 must be approved before this building permit can be approved. Mike Ortiz michael.ortiz@tucsonaz.gov |
||
08/15/2024 | Site Zoning | REQUIRES RESUBMIT | FROM: PDSD Zoning Review Section PROJECT: TC-COM-1023-02505 - TD-DEV-0623-00283 355 N WILMOT RD - C-3 Extended Healthcare Facility (1st Revision, 1st review) TRANSMITTAL DATE: August 15, 2024 COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. COMMENT: Zoning has reviewed the building plan for compliance with TD-DEV-0623-00283 and although it appears that the building plans match the DP Zoning cannot approve the building plans until the revision to the DP is approved by all review agencies. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
07/16/2024 | PDSD Application Completeness | REVIEW COMPLETED |