Permit Number: TC-COM-1023-02470
Parcel: 107143270

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-1023-02470
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2023 PDSD Application Completeness REQUIRES RESUBMIT Please resubmit a gas piping template. Please see the below information for existing commercial gas lines.

The following requirements must be shown on drawing before development services will approve and issue a permit. Drawings must have a minimum text size of 1/8” in all upper case.

1. Project Address
2. Permit Activity number
3. Company name
4. Name of person who prepared the drawing along with date drawing was prepared
5. North arrow
6. Floor plan of building showing location of the gas meter, routes of the gas piping, and the locations of the connected loads
7. Total load on the gas meter (BTUH)
8. Individual connected loads (BTUH)
9. Developed length of pipe
10. Pipe sizes
11. Location of any branch shut-off or automatic valves

Gas piping template sample:
https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/permits/residential-permits/sample_gas_template_0.pdf

Gas piping template:
https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/permits/residential-permits/gas_piping_template.pdf

Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf For questions:building_official@tucsonaz.gov