Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-1023-02459
Parcel: 13317066B

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-1023-02459
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/21/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
03/21/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Correct the arithmetic in the grease interceptor sizing calculations on sheet P2.
2. If the discharge temperature of the dishwasher will be greater than 140 degrees Fahrenheit, show that the temperature rating of the drainage pipe material is suitable for the highest temperature of the wastewater or provide an approved tempering device for the wastewater. Reference: Section 702.5, IPC 2018.
3. An approved 2-way cleanout fitting is allowed to be used at the junction of a building drain and a building sewer, otherwise, cleanouts shall open to allow cleaning only in the direction of flow. Reference: Section 708.1.8, IPC 2018.
4. Provide a vent for the floor drain located in the outside janitor room. Reference: Section 901.2.1, IPC 2018
5. Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6” above the flood rims of the fixtures they protect prior to running horizontally. Reference: Sections 202 (Horizontal Pipe) and 905.4, IPC 2018.
6. Verify that the Pima County Regional Wastewater Reclamation Department will allow the use of an over-sized gravity grease interceptor. Reference: Section 1003.3 (C), IPC 2018, as amended by the City of Tucson.
02/29/2024 PDSD Application Completeness REVIEW COMPLETED