Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3
Permit Number - TC-COM-1023-02459
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/06/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
05/06/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Provide a vent downstream (not upstream) of the new gravity grease separator to protect the seal for the grease separator. Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson. | ||
04/22/2024 | PDSD Application Completeness | REVIEW COMPLETED |