Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1023-02443
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/24/2024 | Site Engineering | APPROVED | |||
04/26/2024 | Site Zoning | APPROVED | |||
04/29/2024 | Commercial Mechanical | NOT REQUIRED | |||
04/29/2024 | Commercial Plumbing | NOT REQUIRED | |||
04/30/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
04/25/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written resonse. 1 Please provide complete electrical power and lighting plans. Include branch circuit designations including Essencial or Emergency branch circuits, panel schedules, compliance with NEC art 517.13 Indicate clearly all light fixture symbols, luminaire schedule and their associated inverter, if appliacble. 2 Provide complete compliance with NEC art 517 as applicable. Ref; 2018 IBC sec. 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
||
04/30/2024 | Commercial Structural | REQUIRES RESUBMIT | Please submit your revised documents along with a detailed response letter, which states how all Building Review Section comments were addressed. 1. Please provide documentation for the Superficial Radiation Therapy Equipment indicating the required level, and method of shielding to be used. IBC 107.2.1 2. Provide ESR number or other approval number and report for the lead lined gypsum board shielding. IBC 107.2.1 Mark Masek Plans Examiner Mark.masek@tucsonaz.gov 520-837-4994 |
||
04/01/2024 | Fire New Construction | REVIEW COMPLETED | |||
03/27/2024 | PDSD Application Completeness | REVIEW COMPLETED |