Permit Number: TC-COM-1023-02443
Parcel: 110072620

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1023-02443
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2024 Site Engineering APPROVED
04/26/2024 Site Zoning APPROVED
04/29/2024 Commercial Mechanical NOT REQUIRED
04/29/2024 Commercial Plumbing NOT REQUIRED
04/30/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
04/25/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written resonse.

1 Please provide complete electrical power and lighting plans. Include branch circuit designations including Essencial or Emergency branch circuits, panel schedules, compliance with NEC art 517.13 Indicate clearly all light fixture symbols, luminaire schedule and their associated inverter, if appliacble.

2 Provide complete compliance with NEC art 517 as applicable.

Ref; 2018 IBC sec. 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
04/30/2024 Commercial Structural REQUIRES RESUBMIT Please submit your revised documents along with a detailed response letter, which states how all Building Review Section comments were addressed.
1. Please provide documentation for the Superficial Radiation Therapy Equipment indicating the required level, and method of shielding to be used. IBC 107.2.1
2. Provide ESR number or other approval number and report for the lead lined gypsum board shielding. IBC 107.2.1

Mark Masek
Plans Examiner
Mark.masek@tucsonaz.gov
520-837-4994
04/01/2024 Fire New Construction REVIEW COMPLETED
03/27/2024 PDSD Application Completeness REVIEW COMPLETED