Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/30/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1.The unit ampacity shown in the equipment schedule shows 90A. This does not correlate with the OCPD shown on the panel schedule. Please clarify.

2. Provide a 120 volt GFI protected receptacle for Mechanical maintenance as required per NEC art 210.63.

Ref; 2018 IBC section 107.2.1, 2017 NEC 408.4.