Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-1023-02427
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/30/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
10/30/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1.The unit ampacity shown in the equipment schedule shows 90A. This does not correlate with the OCPD shown on the panel schedule. Please clarify. 2. Provide a 120 volt GFI protected receptacle for Mechanical maintenance as required per NEC art 210.63. Ref; 2018 IBC section 107.2.1, 2017 NEC 408.4. |
||
10/18/2023 | PDSD Application Completeness | REVIEW COMPLETED |