Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-1023-02426
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/24/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/24/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. Show all 120-volt GFI protected receptacles on the roof for Mechanical maintenance purposes as required per NEC art 210.63. Indicate branch circuit and panel. Correlate the branch circuit with the panel schedule, NEC art 408.4 Ref; 2018 IBC section 107.2.1, 2017 NEC. |
||
| 10/24/2023 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Provide the specifications of the proposed rooftop units. Reference: Section 107.2.1, IBC 2018. 2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018. 3. Show that the proposed rooftop units meet the requirements of Sections C403.3, C403.4, and C403.5 (e.g. provide the mechanical compliance certification from COMcheck). Reference: Section C501.4, International Energy Conservation Code 2018. 4. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson. 5. Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018. |
||
| 10/18/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |