Permit Number: TC-COM-1023-02417
Parcel: 12509012A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1023-02417
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2023 Water - PDSD APPROVED
11/06/2023 Site Engineering NOT REQUIRED
11/06/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
10/24/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 10/24/2023 10:38:55 AM
See the building review comments.



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 10/24/2023 10:36:06 AM
1) General: Include the mechanical, wall, and door (U-Factor) details or COMcheck showing compliance with the 2018 IECC.

2) Sheets A0.0 and P3.0: There are conflicting sprinkler details in the Fire Department Notes #8, General Building Summary, and the Fire Protection Notes on the plumbing sheet. Clarify and coordinate all sprinkler details and if plans are being
deferred, include the sprinklers in the deferred submittal list. (2018 IBC section 107)

3) Sheets A2.1 and A3.0: Provide details of the structure above the outdoor seating and elevation views. Sheet A3.0 note #6 incorrectly identifies it as a diffuser. (2018 IBC section 107)




Mechanical(M) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 10/24/2023 10:36:58 AM
See the building review comments.



Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 10/24/2023 10:36:40 AM
See the building review comments.



Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 10/24/2023 10:38:38 AM
See the building review comments.
11/03/2023 Fire New Construction REQUIRES RESUBMIT Code review states no fire sprinklers, however, fire dept notes state fire sprinklers per NFPA 13. Resolve conflicting information.
john.vincent@tucsonaz.gov
5203495581
11/02/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: TC-COM-1023-02417
2559 E BROADWAY BL Zoning: C-1

TRANSMITTAL DATE:‎November 2, 2023


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT: Clarify the proposed use, If the use is to be a Bar use, TD-DEV-0423-00202 will need to be revised to show the bar use.

If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
10/16/2023 PDSD Application Completeness REVIEW COMPLETED