Permit Number: TC-COM-1023-02412
Parcel: 136260030

Address:
3333 S MANN AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-1023-02412
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2023 Commercial Electrical APPROVED
10/23/2023 Commercial Plumbing APPROVED
10/23/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
10/23/2023 Commercial Mechanical REQUIRES RESUBMIT 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC unit. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
2. Show that the proposed heat pump unit meets the requirements of Sections C403.3, C403.4, and C403.5 (e.g. provide the mechanical compliance certification from COMcheck). Reference: Section C501.4, International Energy Conservation Code 2018.
3. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson.
4. Identify the spaces in which the two remote filter return grilles are located. Recirculation of air from the kitchen is prohibited. Reference: footnote (b), Table 403.3.1.1, IMC 2018.
5. Verify that the proposed make-up air from the new heat pump plus the air transfer from the existing rooftop units is adequate to supply the existing Type I hood. Reference: Section 508.1, IMC 2018.
10/16/2023 PDSD Application Completeness REVIEW COMPLETED