Permit Number: TC-COM-1023-02400
Parcel: 12511210A

Address:
3681 E 4TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.5

Permit Number - TC-COM-1023-02400
Review Name: COMMERCIAL REVIEW - FULL v.5
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/09/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Approved
Reason:
Date Completed : 1/9/2024 12:42:06 PM
Structural review is approved. Subject to the field inspector's approval.



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Approved
Reason:
Date Completed : 1/9/2024 12:39:46 PM
Building review is approved. Subject to the field inspector's approval.



Mechanical(M) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 1/9/2024 12:41:03 PM
1. Resolved - Sheet EMP1: Show toilet room exhaust fan venting to the exterior if window is not operable. (2018 IRC section M1505.2)

2. Unresolved - Sheet EMP1: Include the source of combustion air for water heater. (2018 IRC section G2407) Provide the water heater BTU/h’s to determine the size of the combustion air vent. Section G2407.6 details the calculations for the one-permanent-opening method to be a minimum net ventilation opening of 1 sq inch per 3000 BTU/h.

3. Resolved - Sheet EMP1: Include the details for the heating of the water heater enclosure. (2018 IRC sections 106, P2603.5)




Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 1/9/2024 12:40:35 PM
1. Unresolved - Sheet EMP1: Missing receptacles meeting the location and spacing requirements of 2017 NEC section 210.52. Still missing an exterior receptacle for the porch on the rear of the house. Please refer to section 210.52E(1) and (3). Missing a receptacle within 6ft of the start of the wall between the closet and the opening to the kitchen in the room on the rear of the house.


Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Approved
Reason:
Date Completed : 1/9/2024 12:41:40 PM
Plumbing review is approved. Subject to the field inspector's approval.
01/08/2024 PDSD Application Completeness Express REVIEW COMPLETED