Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.6
Permit Number - TC-COM-1023-02384
Review Name: COMMERCIAL REVIEW - FULL v.6
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/17/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
09/17/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan view comments. 1 Please provide detailed information describing the scope of work, electrical power and lighting work proposed for this project. A description on the plans would be acceptable. 2 Provide complete sealed electrical power and lighting plans. Design and calculations by a registered Engineer registered in the State of Arizona. See the City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf 3 Provide complete compliance with the 2012 City of Tucson Outdoor Lighting Code. Provide complete compliance with the 2018 IECC for the lighting. (Not to be confused with the Outdoor Lighting Code). Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC, 2012 City of Tucson Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements. |
||
09/17/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Comment not addressed. Provide a written response to all comments. [Initial comment: The submitted documents do not show the scope of work for this address or how any of the changes made without permits comply with the adopted building codes. Provide plans sealed by an Arizona Registrant that show how all of the mechanical changes comply to the 2018 International Mechanical Code and the 2018 International Energy Conservation Code. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.] | ||
09/17/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Comment not addressed. Provide a written response to all comments. [Initial comment: The submitted documents do not show the scope of work for this address or how any of the changes made without permits comply with the adopted building codes. Provide plans sealed by an Arizona Registrant that show how all of the plumbing changes comply to the 2018 International Plumbing Code and the 2018 International Energy Conservation Code. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.] | ||
09/17/2024 | Commercial Structural | REQUIRES RESUBMIT | Please submit your revised documents along with a detailed response letter, which states how all Building Review Section comments were addressed. These plans are incomplete and further comments may arise after the original comments are addressed. Please ensure a response letter is submitted addressing all remaining comments. 1. Please see the City of Tucson Commercial Submittal Requirements at https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf and submit a complete set of plans “In accordance with SECTION 107 of the 2018 IBC and the PDSD Building Plan Requirements, complete set of fully dimensioned plans demonstrating the full scope of work shall be provided. All plans must be sealed and signed by an Architect or Engineer registered in the State of Arizona. Note. The term “building plans” may refer to structural, electrical, plumbing, or any other trade regulated by the associated suite of codes adopted by the City of Tucson. Additionally, these building plans should all be in a single pdf. 2. Please provide Copies of energy compliance certificates (COMcheck) for the envelope, mechanical, and interior lighting with next submittal. IBC 107.2.1 3. Sheet Please amend Applicable Codes to include • 2018 International Existing Building Code (IEBC) • 2009 ICC A117.1 Accessibility Code (by reference) • 2018 International Energy Conservation Code (IECC) • City of Tucson/Pima County Outdoor Lighting Code • and include as amended by the City of Tucson. IBC 107.2.1 4. Sheet G1: Please amend plans to include under the Index of Sheets to include the mechanical, plumbing, and electrical sheets. IBC 107.2.1 5. Sheet G1: Please amend plans to indicate the occupancy classification for the fitness center and the occupant load factor used for this occupancy. IBC 107.2.1 a. Additionally, amend plans to provide the total occupancy for the Fitness Center Building as Exercise Rooms and Locker Rooms are calculated using an occupant load factor of 50 gross. IBC 1004.5 6. Please amend plans to provide the existing floor plan to show the floor plan prior to demolition IBC 107.2.1 7. Sheet A3.1 Please amend plans to add a demolition plan to indicate removed walls, ceilings, and any demolition of the existing floor to allow for under slab utilities. For example, under-slab plumbing or electric lines. IBC 107.2.1 8. Sheet A3.1 Please amend Fitness Center Floor plan to include. a. The number of occupants and occupant load factor and square footage is shown for every room and space. IBC 107.2.3, IBC 1004.5 b. The number of occupants being served by each egress door and stairway is shown. IBC 107.2.3 c. Use of each room IBC 107.2.1 d. Provide Emergency Lighting and Exit signs on the plans. IBC 1008, IBC 1013 9. Provide detailed drawings and finish schedule to show compliance with IBC Section 1209 to include finishes required in toilet and bathroom areas. Mark Masek Plans Examiner Mark.masek@tucsonaz.gov 520-837-4994 |
||
08/16/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |