Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1023-02356
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/25/2023 | Site Zoning | APPROVED | |||
11/02/2023 | Water - PDSD | APPROVED | |||
10/30/2023 | Site Engineering | NOT REQUIRED | |||
11/02/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
10/12/2023 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Structural(S) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 10/12/2023 10:55:48 AM See the building review comments Building(B) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 10/12/2023 10:54:22 AM 1) General: The COMcheck is not for the currently adopted 2018 IECC. 2) Sheet M1 (Mechanical Drawings): The outside air is shown being drawn from a garage/storage room and not the exterior. 3) Sheet P1 (Plumbing Drawings): The hand sink and floor sink are not shown connected to the grease interceptor. Amended 2018 IPC section 1003.3 requires all kitchen floor sinks and hand sinks to be connected to the grease trap or a sign stating “HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED.” is placed over the hand sink. 4) Sheet P2 (Plumbing Diagrams): A hand sink and floor sink are not shown on the DWV isometric waste diagram. (2018 IPC section 106.3.1) 5) Sheet E1.0 (Electrical Drawings): Exit sign is not shown in the corridor identifying the means of egress for the storage room and office that is not through the kitchen. (2018 IBC section 1016.2 #5) 6) Sheet E2.0 (Electrical Drawing): Show the transformer does not encroach into the panel's required workspace. (2017 NEC section 110.26(A)) 7) Sheet E2.1 (Electrical Power Drawing): Specify that all kitchen receptacles are GFCI protected not only receptacles within 6ft of sinks. (2017 NEC section 210.8(B)(2)) 8) Sheet E3.0 (Electrical One-Line Diagram): The voltage shown for panel LD (120/240V) does not match the voltages shown on other sheets and details (120/208V). (2018 IBC section 107) Mechanical(M) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 10/12/2023 10:55:15 AM See the building review comments. Electrical(E) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 10/12/2023 10:54:56 AM See the building review comments. Plumbing(P) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 10/12/2023 10:55:32 AM See the building review comments. |
||
10/31/2023 | Fire New Construction | REVIEW COMPLETED | |||
10/09/2023 | PDSD Application Completeness | REVIEW COMPLETED |