Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.4
Permit Number - TC-COM-1023-02356
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/09/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
01/09/2024 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Structural(S) Reviewer Keith Miller kmiller@safebuilt.com Approved Reason: Date Completed : 1/9/2024 11:36:50 AM Structural plans are approved. Subject to the field inspector's approval. Building(B) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 1/9/2024 11:33:00 AM 1. Resolved - General: The COMcheck is not for the currently adopted 2018 IECC. 2. Unresolved - Sheets A3 (Means of Egress), E1.0 (Electrical Drawings): Exit sign is not shown in the corridor identifying the means of egress for the storage room and office that is not through the kitchen. (2018 IBC section 1016.2 #5) Exit signs have been added and still direct occupants through the kitchen. All means of egress paths are to be provided/redirected from all areas that do not travel through the kitchen and the exit signs need to be properly placed (sheets E1.0, A3). Please revise the means of egress travel paths from all areas (offices, storage, and warehouse) on sheet A3 that do not travel through the kitchen and revise the exit sign locations according to the new paths on sheets A3 and E1.0. **The original means of egress path through the main entrance shown on sheet A2 has been changed to direct the occupants through the kitchen (sheet A3) which is prohibited. ** Mechanical(M) Reviewer Keith Miller kmiller@safebuilt.com Approved Reason: Date Completed : 1/9/2024 11:35:30 AM Mechanical plans are approved. Subject to the field inspector's approval. Electrical(E) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 1/9/2024 11:33:35 AM 1) Unresolved - Sheets A3 (Means of Egress), E1.0 (Electrical Drawings): Exit sign is not shown in the corridor identifying the means of egress for the storage room and office that is not through the kitchen. (2018 IBC section 1016.2 #5) Exit signs have been added and still direct occupants through the kitchen. All means of egress paths are to be provided/redirected from all areas that do not travel through the kitchen and the exit signs need to be properly placed (sheets E1.0, A3). Please revise the means of egress travel paths from all areas (offices, storage, and warehouse) on sheet A3 that do not travel through the kitchen and revise the exit sign locations according to the new paths on sheets A3 and E1.0. **The original means of egress path through the main entrance shown on sheet A2 has been changed to direct the occupants through the kitchen (sheet A3) which is prohibited. ** 2) Resolved - Sheet E2.0 (Electrical Drawing): Show the transformer does not encroach into the panel's required workspace. (2017 NEC section 110.26(A)) 3) Resolved - Sheet E2.1 (Electrical Power Drawing): Specify that all kitchen receptacles are GFCI protected not only receptacles within 6ft of sinks. (2017 NEC section 210.8(B)(2)) 4) Resolved - Sheet E3.0 (Electrical One-Line Diagram): The voltage shown for panel LD (120/240V) does not match the voltages shown on other sheets and details (120/208V). (2018 IBC section 107) Plumbing(P) Reviewer Keith Miller kmiller@safebuilt.com Approved Reason: Date Completed : 1/9/2024 11:36:13 AM Plumbing plans are approved. Subject to the field inspector's approval. |
||
01/05/2024 | PDSD Application Completeness | REVIEW COMPLETED |