Permit Number: TC-COM-1023-02356
Parcel: 103090310

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-1023-02356
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
11/30/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/29/2023 3:32:12 PM
See the building review comments.



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/29/2023 3:30:51 PM
1) Resolved - General: The COMcheck is not for the currently adopted 2018 IECC.
2) Resolved - Sheet M1 (Mechanical Drawings): The outside air is shown being drawn from a garage/storage room and not the exterior.

3) Resolved - Sheet P1 (Plumbing Drawings): The hand sink and floor sink are not shown connected to the grease interceptor. Amended 2018 IPC section 1003.3 requires all kitchen floor sinks and hand sinks to be connected to the grease trap or a sign stating “HANDWASH SINK ONLY! NO FOOD PREPARATION OR ISHWASHING ALLOWED.” is placed over the hand sink.

4) Resolved - Sheet P2 (Plumbing Diagrams): A hand sink and floor sink are not shown on the DWV isometric waste diagram. (2018 IPC section 106.3.1) The fixtures are still not included in the diagram.

5) Unresolved - Sheets A3 (Means of Egress), E1.0 (Electrical Drawings): Exit sign is not shown in the corridor identifying the means of egress for the storage room and office that is not through the kitchen. (2018 IBC section 1016.2 #5) Exit signs have been added and still direct occupants through the kitchen. All means of egress paths are to be provided/redirected from all areas that do not travel through the kitchen and the exit signs need to be properly placed (sheets E1.0, A3). Please revise the means of egress travel paths from all areas (offices, storage, and warehouse) on sheet A3 that do not travel through the kitchen and revise the exit sign locations according to the new paths on sheets A3 and E1.0.

6) Resolved - Sheet E2.0 (Electrical Drawing): Show the transformer does not encroach into the panel's required workspace. (2017 NEC section 110.26(A))

7) Resolved - Sheet E2.1 (Electrical Power Drawing): Specify that all kitchen receptacles are GFCI protected not only receptacles within 6ft of sinks. (2017 NEC section 210.8(B)(2))

8) Resolved - Sheet E3.0 (Electrical One-Line Diagram): The voltage shown for panel LD (120/240V) does not match the voltages shown on other sheets and details (120/208V). (2018 IBC section 107)



Mechanical(M) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/29/2023 3:31:41 PM
See the building review comments.



Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/29/2023 3:31:24 PM
See the building review comments.



Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/29/2023 3:31:57 PM
See the building review comments.
11/29/2023 PDSD Application Completeness REVIEW COMPLETED