Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESTAMP - COMMERCIAL v.1
Permit Number - TC-COM-1023-02339
Review Name: RESTAMP - COMMERCIAL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/07/2024 | Commercial Building | APPROVED | |||
02/07/2024 | Commercial Electrical | APPROVED | |||
02/06/2024 | Commercial Plumbing | APPROVED | |||
02/05/2024 | Site Zoning | APPROVED | |||
02/07/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
02/06/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Provide structural calculations and details to show how the computer room air conditioning unit is connected to the building structure. Reference: Section 302.1, IMC 2018. | ||
02/06/2024 | Fire New Construction | REVIEW COMPLETED |