Permit Number: TC-COM-1023-02339
Parcel: 117121080

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1023-02339
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2023 Commercial Mechanical APPROVED
10/18/2023 Site Zoning APPROVED
10/30/2023 Site Engineering NOT REQUIRED
11/08/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
11/08/2023 Commercial Structural REQUIRES RESUBMIT Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed.
1. Expand the information on Sheet A100- Floor Plan to clarify the area, occupancy type, design occupant load for each room or space shown on the plan. The sums of each category should match the Occupant Load Table on Sheet T1. This information is partially shown on the Floor Plan, however, information missing for the areas of alteration and some existing rooms and spaces. Please ensure the Occupant Load Table on sheet T1 and the design occupant load on sheet A100 are the same. IBC 1004, IBC 107.2
10/13/2023 Fire New Construction REVIEW COMPLETED
10/05/2023 PDSD Application Completeness REVIEW COMPLETED