Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1023-02339
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/30/2023 | Commercial Mechanical | APPROVED | |||
10/18/2023 | Site Zoning | APPROVED | |||
10/30/2023 | Site Engineering | NOT REQUIRED | |||
11/08/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/08/2023 | Commercial Structural | REQUIRES RESUBMIT | Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. 1. Expand the information on Sheet A100- Floor Plan to clarify the area, occupancy type, design occupant load for each room or space shown on the plan. The sums of each category should match the Occupant Load Table on Sheet T1. This information is partially shown on the Floor Plan, however, information missing for the areas of alteration and some existing rooms and spaces. Please ensure the Occupant Load Table on sheet T1 and the design occupant load on sheet A100 are the same. IBC 1004, IBC 107.2 |
||
10/13/2023 | Fire New Construction | REVIEW COMPLETED | |||
10/05/2023 | PDSD Application Completeness | REVIEW COMPLETED |