Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.4
Permit Number - TC-COM-1023-02336
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.4
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/05/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
12/05/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. Ref; Plan Sheet ‘PH-1’, Parcel size note. The total lumens allowed should reflect that of the total parcel size of 10.78 acres, not 7.1. Please revise the lumen calculations to show correct values. OLC section 104.2.1. When resubmitting, be sure to submit all plan documents. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code (OLC). |
||