Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/18/2023 Commercial Mechanical REQUIRES RESUBMIT 1. Provide construction documents drawn to scale and with sufficient detail and clarity to demonstrate that the work complies with the applicable codes. The information shall, as a minimum, include the proposed location of the new condensing unit, any structural changes necessitated by the location of the condensing unit, any electrical changes resulting from adding the new split system, complete specifications for the new heating equipment, provisions for condensate disposal, and provisions for mechanical ventilation of the dwelling unit. Reference: Section 107.2.1, IBC 2018.
2. Provide the specifications for the proposed new AC system. The system shall comply with Sections R403.1 and R503.1.2, IECC 2018 and shall comply with the Department of Energy efficiency requirements that went into effect on January 1, 2023.
10/18/2023 Commercial Plumbing REQUIRES RESUBMIT Clarify the scope of work for plumbing changes, if any. Reference Section 107.2.1, IBC 2018.
10/03/2023 PDSD Application Completeness Express REVIEW COMPLETED