Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-1023-02328
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/09/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
10/09/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. Please update the Registrant Seals and cloud any changes from the last permit/plan submittal. Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC |
||
10/03/2023 | PDSD Application Completeness | REVIEW COMPLETED |