Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: TC-COM-1023-02314
Parcel: 121080080

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1023-02314
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2023 Water - PDSD APPROVED
10/23/2023 Site Engineering NOT REQUIRED
10/27/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/18/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 10/13/2023 2:11:23 PM



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 10/13/2023 3:29:10 PM



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 10/4/2023 5:39:37 PM
As per 2018 IMC Table 403.3.1.1 - Pet shops (animal areas)b. Note b states "Mechanical exhaust required and the recirculation of air from such places is prohibited. Recirculation of air that is contained completely within such spaces shall
not be prohibited. (See section 403.2.1, item 3).

RTUs #6 supplies and returns air to animal areas and reception area. RTU #7 supplies and returns air to animal areas and Kitchen and Break Room This is prohibited by 2018 IMC Table 403.3.1.1 - Pet shops (animal areas)b



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 10/14/2023 1:45:00 PM
Electrical Review Paw Commons Pet Resort
By: Ron Ross PE
E2.0 ELECTRICAL POWER FLOOR PLAN: Need to show compliance with NEC 210.8 by calling out GFCI receptacles or having GFCI circuit breakers for all receptacles within 6 foot of a sink or water source ie Wash Room receptacles should be GFCI protected.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 10/17/2023 10:43:42 PM
First Plumbing Review:
1). This occupancy type & load requires a high/low drinking fountain. update all affected pages -IPC 403.1

2). Floor sinks in grooming rooms on plan pages P1.1 & P2.0 needs to connect to a hair interceptor -IPC 1003.1

3). What is the use of the various floor sinks not located near any indirect discharging fixtures or appliances on plan pages P1.1 & P2.0 ? -IPC 106.3.1, 801.1

4). Show the Gas water heater intake & exhaust routing within the plumbing or mechanical pages. -IFGC 304, 503.1
10/20/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-1023-02314
6211 E. Speedway Bl. – C-2
Animal Service (1st Review)

TRANSMITTAL: October 20, 2023

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in C-2 zone (UDC 4.7.21), Animal Service – Boarding is a permitted use in the zone (UDC Table 4.8-4) as a [2] Zoning Examiner Special Exception Procedure, Section 3.4.3, subject to Use Specific Standards 4.9.4.D.9 - .15.

1. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. AM 2-06 can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes-and-Plans/Zoning-Code.

2. The Zoning Examiner Special Exception Procedure shall be approved prior to approval of the DP & building plan..

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
10/25/2023 Fire New Construction REVIEW COMPLETED
10/03/2023 PDSD Application Completeness Express REVIEW COMPLETED