Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: TC-COM-1023-02314
Parcel: 121080080

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-1023-02314
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/29/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-1023-02314
6211 E. Speedway Bl. – C-2
Animal Service (3rd Review)

TRANSMITTAL: December 29, 2023

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in C-2 zone (UDC 4.7.21), Animal Service – Boarding is a permitted use in the zone (UDC Table 4.8-4) as a [2] Zoning Examiner Special Exception Procedure, Section 3.4.3, subject to Use Specific Standards 4.9.4.D.9 - .15.

1. As Development Package (DP) TD-DEV-1123-00443 has not yet completed the first review Zoning cannot compare the plans for compliance with each other. Zoning will review the building plans on the next submittal.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
01/02/2024 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer (from previous submittal TUC9414001.100323)
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 10/13/2023 2:11:23 PM



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 10/13/2023 3:29:10 PM




Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 11/17/2023 7:00:12 PM

1. As per 2018 IMC Table 403.3.1.1 - Pet shops (animal areas)b. Note b states "Mechanical exhaust required and the recirculation of air from such places is prohibited. Recirculation of air that is contained completely within such spaces
shall not be prohibited. (See section 403.2.1, item 3). (RESOLVED)

2. RTUs #6 supplies and returns air to animal areas and reception area. RTU #7 supplies and returns air to animal areas and Kitchen and Break Room This is prohibited by 2018 IMC Table 403.3.1.1 - Pet shops (animal areas)b (RESOLVED)



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 11/17/2023 2:40:36 PM




Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 12/30/2023 3:06:06 PM
Third Plumbing Review: OK Subject to field inspections

Resolved-1). This occupancy type & load requires a high/low drinking fountain. update all affected pages -IPC 403.1

2). Resolved-Floor sinks in grooming rooms on plan pages P1.1 & P2.0 needs to connect to a hair interceptor -IPC 1003.1 ** Grooming room wash tubs or floor sink still need hair interceptor(S)**

3). Resolved-What is the use of the various floor sinks not located near any indirect discharging fixtures or appliances on plan pages P1.1 & P2.0 ? -IPC 106.3.1, 801.1

4). Resolved-Show the Gas water heater intake & exhaust routing within the plumbing or mechanical pages. -IFGC 304, 503.1
12/22/2023 PDSD Application Completeness Express REVIEW COMPLETED