Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1022-00009
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/16/2022 | Commercial Electrical | APPROVED | |||
| 12/30/2022 | Commercial Structural | APPROVED | |||
| 11/02/2022 | Site Zoning | APPROVED | |||
| 11/22/2022 | Site Engineering | NOT REQUIRED | |||
| 12/30/2022 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/14/2022 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Show that the proposed replacement HVAC units meet the requirements of Sections C403.3, C403.4, and C403.5 (e.g. provide the mechanical compliance certification from COMcheck). Reference: Section C501.4, International Energy Conservation Code 2018. 2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018. 3. Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018. 4. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the restroom lights are off). Reference: Section 403.2.1 (4), IMC 2018 |
||
| 12/15/2022 | Commercial Plumbing | REQUIRES RESUBMIT | Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. | ||
| 12/02/2022 | Fire New Construction | REVIEW COMPLETED | |||
| 11/01/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |