Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/09/2023 Commercial Mechanical REQUIRES RESUBMIT Revised drawings not submitted. [Initial comment: Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the restroom lights are off). Reference: Section 403.2.1 (4), IMC 2018.]
02/09/2023 Commercial Plumbing REQUIRES RESUBMIT Revised drawings not submitted. [Initial comment: Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.]