Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0926-01622
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/16/2026 | Commercial Building | APPROVED | |||
| 10/14/2026 | Commercial Electrical | APPROVED | Approved with comment added to plans: Equipment rated for wet/damp areas, NEC 406.9 |
||
| 10/07/2026 | Site Engineering | NOT REQUIRED | |||
| 10/16/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/15/2026 | Addressing Validation | REQUIRES RESUBMIT | The address on the permit is 6630 E TANQUE VERDE RD, however on page M101 of the construction plans the address is 6626 E TANQUE VERDE RD. If the address on the permit is incorrect, please submit a change of address request. Once this review is complete, please resubmit the construction plans with correct address on every page. | ||
| 10/15/2026 | Commercial Mechanical | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0926-01622 ADDRESS/PARCEL: 6630 E TANQUE VERDE RD TUCSON, AZ 85715 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov. COMMENTS: 1. Please indicate the required supply air cfm at each supply diffuser/grille on the mechanical floor plan for use during system balancing and verification. Reference: Section 107.2.1, IBC 2024. |
||
| 10/15/2026 | Commercial Plumbing | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0926-01622 ADDRESS/PARCEL: 6630 E TANQUE VERDE RD TUCSON, AZ 85715 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov. COMMENTS: 1. Please revise the plumbing fixture schedule to clarify the water supply fixture unit values assigned to the four bathtubs (public), currently listed as 2.0 fixture units each. Table 610.3 of the 2024 UPC and Table E103.3(2) of Appendix E of the 2024 IPC list a public bathtub as 4.0 fixture units. Please clarify also which code is being used and revise the fixture schedule and water demand calculations accordingly. Reference: Section 604.1 and Table E103.3(2), IPC 2024. Table 610.3, UPC 2024. |
||
| 10/14/2026 | Site Zoning | REQUIRES RESUBMIT | PDSD TRANSMITTAL FROM: Jeffrey W. Cassidy, Planner I Planning & Development Services Department – Current Zoning Review Section, Commercial PROJECT: TC-COM-0926-01622 – Commercial – C of O for Pet Salon 6630 E TANQUE VERDE RD TUCSON, AZ 85715 (C-2 Zoning) Certificate of Occupancy Review – 1st Review TRANSMITTAL DATE: October 14, 2026 1. COMMENT: The suite indicated in the drawing set is for 6628 (as opposed to the 6630 applied for on the permit); Update drawing set to reflect correct address in title block. 2. COMMENT: Per UDC TABLE 7.4.4-1 and the square footage of the 6628 address in the drawing set, provide a note that indicates compliance with the 1 vehicular parking stall per 400 square feet of gross floor area. 3. COMMENT: Additional comments may be forthcoming on the next review based on responses to Zoning and other PDSD reviewer comments. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: 4. COMMENT: Corrected certificate of occupancy permit. 5. COMMENT: Provide a detailed response letter with your submittal that clearly shows how you have addressed all Zoning comments. To resubmit visit Tucson Development Center at https://tdc-online.tucsonaz.gov/#/home . Instructions for resubmittal - https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/old-pdfs/double-old/resubmittals.pdf If you have any questions about this transmittal, please contact jeffrey.cassidy@tucsonaz.gov The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code . |
||
| 10/15/2026 | Water - PDSD | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0926-01622 ADDRESS/PARCEL: 6630 E TANQUE VERDE RD TUCSON, AZ 85715 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov. COMMENTS: 1. Tucson Water limits a 5/8” meter to a maximum demand of 20 GPM. Provide a letter from Tucson Water confirming that the use of a 5/8” water meter will be allowed for this project. |
||
| 10/16/2026 | Fire New Construction | REVIEW COMPLETED | |||
| 10/02/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |