Permit Number: TC-COM-0926-01621
Parcel: 125091130

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0926-01621
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2026 Design Review Standard NOT REQUIRED It appears the proposal does not require a Sunshime Mile District (SMD) application. Zoning has informed the site is currently being used for a medical spa and the applicant for the building permit has an email address that matches the name of the current business. medical spa is considered Personal Services land use, and Zoning has identified a Certificate of Occupancy from 2017 for a Salon and Spa, also a Personal Services land use, so the proposed medical spa does not represent a change of use.
10/27/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
10/21/2026 Site Engineering Standard NOT REQUIRED
11/12/2026 Commercial Post Review Express PENDING ASSIGNMENT
11/09/2026 Addressing Validation REQUIRES RESUBMIT If you have any questions, please contact cdrc@tucsonaz.gov

There appear to be two unit numbers attached to this address. A change of address request is required to add the correct unit number to this permit. When the address change is applied for, please resubmit plans with the updated address.

Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf


Instructions can be found here to request change of address: https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/sub-records.pdf
10/27/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit a complete set of revised/corrected documents and a written response addressing each review comment and explaining how it was resolved. Please note that the original submittal was incomplete, and the review was based on the information provided. Additional comments may be issued upon subsequent review.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov

Registered Design Professional Documents Required for Certificate of Occupancy
1. The documents submitted to demonstrate compliance for issuance of a Certificate of Occupancy (C of O) shall be prepared, signed, and sealed by an architect or engineer registered in the State of Arizona. Submit the following complete documents:
A. Code Analysis: Identify the proposed use and occupancy classification, construction type, occupant load, means of egress, accessibility requirements, and applicable building code provisions. Additionally, provide the floor location, Are Fire Sprinklers provided? Is a Fire alarm provided?
B. Site Plan: Provide a complete, site plan identifying the building, and the location of this tenant space, access routes, parking, and other applicable site features.
C. Floor Plan: Provide a complete, dimensioned floor plan identifying room uses, occupant loads, doors, and other applicable building features.
D. Egress Plan: Identify the required means of egress, exit locations, exit widths, occupant loads, travel distances, and other applicable egress requirements.
All documents shall be sufficiently detailed to demonstrate compliance with the 2024 International Building Code and applicable City requirements.
Code Reference: 2024 IBC Sections 107.1, 107.2.1, 107.2.3, and 107.2.6, as applicable.

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
10/27/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0926-01621 (2825 E BROADWAY BL TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Existing Building Code (IEBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Change of occupancy from Spa to Medical use.
2. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
3. Provide electrical plans as part of this CofO submission. Show existing electrical meets the requirements of the International Existing Building Code, chapter 10, IEBC 1007.1.
4. Change of occupancy to a Health Care Facility, requires all related electrical to be brought up to the latest 2023 NEC requirements for health care facilities.
5. Provide electrical sheets sealed, dated and signed by an Arizona Registered Electrical Engineer.
10/27/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0926-01621
ADDRESS/PARCEL: 2825 E BROADWAY BL TUCSON, AZ 85716

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Please provide mechanical plans showing the existing mechanical system configuration, including the location of all existing equipment and demonstrating that the space is conditioned and meets minimum ventilation requirements for the proposed outpatient clinic. Plans must be sealed by an Arizona-registered design professional. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
10/27/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0926-01621
ADDRESS/PARCEL: 2825 E BROADWAY BL TUCSON, AZ 85716

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Provide plumbing plans showing all existing plumbing fixtures, equipment, building sewer, water service, and related piping. Plans must be sealed by an Arizona-registered design professional. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Please provide a code analysis on the drawings identifying the occupancy classification, occupant load, and the minimum number of required plumbing fixtures for the proposed use. Reference: Sections 302.1, 1004, and 2902.1, 2024 IBC.
11/12/2026 Fire New Construction Standard REQUIRES RESUBMIT Resolve building review comments.
Questions: patricia.shelton@tucsonaz.gov
11/09/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Jeffrey W. Cassidy, Planner I
Planning & Development Services Department – Current Zoning Review Section, Commercial

PROJECT:
TC-COM-0926-01621 – Commercial – C of O for Medical Office Outpatient Clinic
2825 E BROADWAY BL TUCSON, AZ 85716 (C-2 Zoning)
Certificate of Occupancy Review – 1st Review

TRANSMITTAL DATE:
November 09, 2026

1. COMMENT: Per https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Occupancy-Certificates#section-1 the application is incomplete. Update per the following comments:

2. COMMENT: In the narrative, the customer acknowledges the proposed Certificate of Occupancy (C of O) is for one of the two existing suites. Indicate a) on the drawings and b) the permit, what the suite number is for this C of O.

3. COMMENT: The overall square footage of the building was provided but further breakdown of the square footage of the intended suite will be required in order to determine parking requirements, etc. Provide square footage of the suite intended for this C of O.

3. COMMENT: The previous use (Salon and Spa) had a parking intensity of one parking stall per 300 square feet. The proposed medical office-outpatient use commands a more intense ratio of one parking stall per 200 square feet. Indicate the appropriate number of parking spaces on the missing site plan and provide a parking table of parking spaces required and parking spaces provided.

4. COMMENT: Drawings must be prepared and stamped by a registered Arizona architect or engineer. There is no evidence (stamp with license number by registered professional, company name, company contact information) of a licensed professional throughout the drawing set.

5. COMMENT: A site plan was not provided. Provide the following:

1) Legal Description
2) Parcel Number
3) Address
4) Existing Zoning Classification and zoning classifications surrounding the property.
5) Example Site Plan: https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/plan-samples/full-site-plan_feb2026.pdf

6. COMMENT: Provide Zoning Use General Note: Commercial Services Use – Medical Services, Outpatient subject to use specific standards 4.9.4.O.2 and 4.9.13.O.

7. COMMENT: Additional comments may be forthcoming on the next review based on responses to Zoning and other PDSD reviewer comments.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:

8. COMMENT: Corrected certificate of occupancy permit.

9. COMMENT: Provide a detailed response letter with your submittal that clearly shows how you have addressed all Zoning comments.

To resubmit visit Tucson Development Center at https://tdc-online.tucsonaz.gov/#/home .

Instructions for resubmittal - https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/old-pdfs/double-old/resubmittals.pdf

If you have any questions about this transmittal, please contact jeffrey.cassidy@tucsonaz.gov

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code .
10/27/2026 Water - PDSD Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0926-01621
ADDRESS/PARCEL: 2825 E BROADWAY BL TUCSON, AZ 85716

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand that will be served by the water meter. Reference: Section 107.2.1, IBC 2024.
10/21/2026 PDSD Application Completeness Express REVIEW COMPLETED