Permit Number: TC-COM-0926-01611
Parcel: 12607033D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.3

Permit Number - TC-COM-0926-01611
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/12/2026 Commercial Building APPROVED
11/10/2026 Commercial Plumbing APPROVED
10/29/2026 Site Engineering APPROVED
11/12/2026 Site Zoning APPROVED
11/13/2026 Commercial Post Review Express PENDING ASSIGNMENT
11/02/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0926-01611 (306 N ALVERNON WY TUCSON, AZ 85711)
2nd Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

>>> Electrical comments were not fully addressed.

1. Provide an electrical plan showing any/all electrical work. Plans shall include but may not be limited to items below and as necessary for the actual scope of work:
2. Electrical demo plans.
3. Provide an electrical panel schedule and designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1.
4. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type.
5. Note that all demo’ed and capped electrical shall be done in a code compliant location such as an existing junction box or other readily accessible location. NEC 300.15
6. Provide GFCI per NEC 210.8(B) and (D). GFCI protection for the drinking fountain is required.
11/13/2026 Fire New Construction REVIEW COMPLETED
10/29/2026 PDSD Application Completeness Express REVIEW COMPLETED