Permit Number: TC-COM-0926-01611
Parcel: 12607033D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0926-01611
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2026 Water - PDSD APPROVED
10/13/2026 Commercial Mechanical NOT REQUIRED
10/12/2026 Commercial Building REQUIRES RESUBMIT Please submit a complete set of revised/corrected documents and a written response addressing each review comment and explaining how it was resolved. Please note that the original submittal was incomplete, and the review was based on the information provided. Additional comments may be issued upon subsequent review.

Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Cover Sheet: Please provide a Building number, for the building in this permit, as a part of the address. IBC Section 107.2.1
2. Cover Sheet: Please revise the plans to identify the location of the toilet facilities to be used by building occupants and indicate the distance from the building to those facilities, in accordance with 2024 IBC Section 2902.3.3.
3. Cover Sheet: Please revise the List of Drawings to match the submitted construction documents. The cover sheet is included but not listed, while Sheets A-9 and A-9A are listed but not provided. Please submit a corrected sheet index and a complete, coordinated plan set that includes all listed sheets, in accordance with 2024 IBC Section 107.2.1.
4. Sheet A-10: Please revise the drawings to provide a clear 5′ × 5′ ramp landing at the door, free of encroachment from the guard/handrail assembly, in accordance with 2024 IBC Section 1012.6.4. Also, indicate that the landing slope shall not exceed 2% in any direction, per 2024 IBC Section 1012.6.1.
4. Sheet A-10: Please indicate the total ramp rise and provide handrails on both sides where the rise exceeds 6 inches, per 2024 IBC Section 1012.8. Provide details for handrail height, continuity, extensions, and terminations in accordance with Sections 1014.2, 1014.4, and 1014.7. Handrail extensions shall return to the guard or ramp.
Provide a detailed cross-section of the Type II handrail demonstrating that corners and edges have a minimum radius of 0.01 inch and are not sharp, per 2024 IBC Section 1014.4.2.
5. Sheet A-10: Please provide construction details and structural calculations showing how the handrail/guard assembly and its attachments resist a 200-pound concentrated load and a 50-pound-per-linear-foot uniform load, in accordance with 2024 IBC Sections 1607.9.2 and 1607.9.1.1.

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
10/13/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0926-01611 (306 N ALVERNON WY TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide an electrical plan showing any/all electrical work. Plans shall include but may not be limited to items below and as necessary for the actual scope of work:
2. Electrical demo plans.
3. Provide an electrical panel schedule and designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1.
4. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type.
5. Provide GFCI per NEC 210.8(B) and (D). GFCI protection for the drinking fountain is required.
10/13/2026 Commercial Plumbing REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0926-01611
ADDRESS/PARCEL: 306 N ALVERNON WY TUCSON, AZ 85711

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Sheet A2 indicates that the plumbing is to be capped back to the floor and the existing cold water line used for the new water filter. However, the Brio CLPOU730UVRO4 appears to require a drain connection per the manufacturer's installation instructions. Please provide a detail showing how the water filter will be connected and installed in accordance with the manufacturer's installation instructions. Reference: Section 107.2.1, IBC 2024.
10/15/2026 Fire New Construction REQUIRES RESUBMIT Resolve building review comments.
Questions: patricia.shelton@tucsonaz.gov
10/07/2026 Site Engineering REQUIRES RESUBMIT TC-COM-0926-01611 – 26.10.07
Permit Activity Number: TC-COM-0926-01611 (1st Review)
Project: ALTERATION LEVEL 2; MINOR ALTERATION OF EXISTING FITNESS CENTER. SPACE TO RECEIVE NEW FLOORING, PAINT, MOULDING, LIGHTING, AND EQUIPMENT. EXISTING RESTROOM TO BE REMOVED, PLUMBING AND ELECTRICAL TO BE CAPPED
Location: 306 N ALVERNON WY
Review Date: 10/07/2026
Reviewer: John Mounsey – Engineering Associate
Reviewer Contact Information: john.mounsey@tucsonaz.gov

Site Engineering Comments:
1. The exterior ramp requires a level landing at the top, minimum 60" clear in the direction of travel and at least as wide as the ramp run (ICC A117.1 405.7). Revise the plans to show the 60" clear dimension, with guards, walls, and door swing located outside of it.
10/13/2026 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Jeffrey W. Cassidy, Planner I
Planning & Development Services Department – Current Zoning Review Section, Commercial

PROJECT:
TC-COM-0926-01611 – Commercial – LEVEL 2; MINOR ALTERATION OF EXISTING FITNESS CENTER
306 N ALVERNON WY TUCSON, AZ 85711 (C-1 Zoning)
Commercial Building Plan Review – 1st Review

TRANSMITTAL DATE:
October 13, 2026

1. COMMENT: Update the sheet index to account for all sheets provided (Including cover sheet).

2. COMMENT: Additional comments may be forthcoming on the next review based on responses to Zoning and other PDSD reviewer comments.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:

3. COMMENT: Corrected commercial building permit.

4. COMMENT: Provide a detailed response letter with your submittal that clearly shows how you have addressed all Zoning comments.

To resubmit visit Tucson Development Center at https://tdc-online.tucsonaz.gov/#/home .

Instructions for resubmittal - https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/old-pdfs/double-old/resubmittals.pdf

If you have any questions about this transmittal, please contact jeffrey.cassidy@tucsonaz.gov

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code .
10/01/2026 PDSD Application Completeness Express REVIEW COMPLETED