Permit Number: TC-COM-0926-01591
Parcel: 10513030A

Address:
345 E ROGER RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0926-01591
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2026 Commercial Building Standard APPROVED
10/14/2026 Commercial Electrical Standard APPROVED
10/15/2026 Site Zoning Standard APPROVED
10/14/2026 Outdoor Lighting Standard NOT REQUIRED
09/28/2026 Site Engineering Standard NOT REQUIRED
10/18/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/12/2026 Fire New Construction Standard REQUIRES RESUBMIT Per 22024 IFC 1205.3.1, Perimeter Pathways. There shall be a minimum 6 foot wide clear perimeter around the edges of the roof.
Exception: Where either axis of the building is 250 feet or less, the clear perimeter around the edges of the roof shall be permitted to be reduced to a minimum width of 4 feet.
*Please provide a minimum of 4 feet around the perimeter of the roof. Not just the two ends and the ridge.
If you have questions or concerns on this, please reach out to me.

Ryan P Johnson
Tucson Fire Department
Fire Protection Plans Examiner
(520)539-5370
Ryan.Johnson@Tucsonaz.gov
09/28/2026 PDSD Application Completeness Express REVIEW COMPLETED