Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0926-01591
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/18/2026 | Commercial Building Standard | APPROVED | |||
| 10/14/2026 | Commercial Electrical Standard | APPROVED | |||
| 10/15/2026 | Site Zoning Standard | APPROVED | |||
| 10/14/2026 | Outdoor Lighting Standard | NOT REQUIRED | |||
| 09/28/2026 | Site Engineering Standard | NOT REQUIRED | |||
| 10/18/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/12/2026 | Fire New Construction Standard | REQUIRES RESUBMIT | Per 22024 IFC 1205.3.1, Perimeter Pathways. There shall be a minimum 6 foot wide clear perimeter around the edges of the roof. Exception: Where either axis of the building is 250 feet or less, the clear perimeter around the edges of the roof shall be permitted to be reduced to a minimum width of 4 feet. *Please provide a minimum of 4 feet around the perimeter of the roof. Not just the two ends and the ridge. If you have questions or concerns on this, please reach out to me. Ryan P Johnson Tucson Fire Department Fire Protection Plans Examiner (520)539-5370 Ryan.Johnson@Tucsonaz.gov |
||
| 09/28/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |