Permit Number: TC-COM-0926-01581
Parcel: 11706081G

Address:
400 N TOOLE AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0926-01581
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/29/2026 Commercial Mechanical Express REQUIRES RESUBMIT 1. Provide a mechanical design for the installation of the kitchen equipment, performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work. Reference: Sections 107.1 and 107.2.1, IBC 2024.
2. The proposed electric deck-type oven is listed and labeled in accordance with UL 197 for reduced grease emissions (less than 5 mg/cubic meter) and no visible smoke emissions. Either a Type II hood or the oven manufacturer’s direct ventilation system will be required to exhaust the ambient heat and steam generated by the oven. Reference: Sections 507.1 and 507.3, IMC 2024.

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
09/25/2026 PDSD Application Completeness Express REVIEW COMPLETED