Permit Number: TC-COM-0926-01576
Parcel: 12511201A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0926-01576
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2026 Commercial Electrical NOT REQUIRED
09/29/2026 Commercial Mechanical NOT REQUIRED
09/29/2026 Commercial Plumbing NOT REQUIRED
09/28/2026 Site Engineering NOT REQUIRED
10/09/2026 Site Zoning NOT REQUIRED Disregard 'New' Site Plan Notes 10 thru 13 as customer states the only scope is Hand Railing Replacement (in titleblock).
09/29/2026 Water - PDSD NOT REQUIRED
10/09/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/25/2026 Addressing Validation REQUIRES RESUBMIT If you have any questions, please contact cdrc@tucsonaz.gov

The address on the permit does not match the address on the plans. The address on the permit is 3660 E 3RD ST Building 4, however the address on the plans is 3660 E 3RD ST. Please resubmit Site plan and include Building number after this initial review is complete.

Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf
09/29/2026 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.

Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov

1. Provide architectural plans for the proposed work. The submitted structural calculations/details indicate deck repairs; however, the permit description only states “Repair existing railings,” and no architectural plans were submitted. Clearly identify the existing and proposed deck and railing repairs, including locations, dimensions, materials, and construction details. Revise the permit scope/description to accurately identify all work proposed. 2024 IBC 105.3.1, 107.2.1; 2024 IEBC 501.1.

2. Indicate if the workk has already been completed and the special inspection appears to indicate. IBC 107.2.1

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
10/05/2026 Fire New Construction REQUIRES RESUBMIT -Please resolve all building comments.
john.vincent@tucsonaz.gov
5203495581
09/25/2026 PDSD Application Completeness Express REVIEW COMPLETED