Permit Number: TC-COM-0926-01561
Parcel: 135112540

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0926-01561
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/17/2026 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0926-01561 (7543 E GOLF LINKS RD TUCSON, AZ 85730)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Please refrain from resubmitting a full set of PV plans, the plans submitted must only include the scope of work. Plans including the PV will not be accepted as this is outside of the scope of this permit.
2. Mark only what is being covered under this permit as ‘New’. Everything else should be shown as ‘Existing’.
3. Provide Service Surge Protection per NEC 230.67(D). All downstream dwelling units require surge protection when replacing the service equipment.
09/17/2026 PDSD Application Completeness Express REVIEW COMPLETED